Check the set before the reviewer does.
Print this. Check the items that are actually on your set. Unchecked boxes are usually the comment letter. Educational — not a permit, not a completeness stamp.
Use the matching field tool, then send the share link. Florida PE 95945 does not certify this list against your project.
Before you upload
- Occupancy, area, people, and OA method on an M-sheet — not “OA per code.” OA estimator · 401 vs 403
- Kitchen: Type I vs II from the menu, grease duct, 508 makeup air, 506.3.13 termination. Hood · 508 · termination
- Hood on M-sheets and grease interceptor path on P-sheets. Coordination
- Garage: continuous vs automatic, Full-On / Standby rates. 404
- Combustion air method and 303 room name. Chapter 7 · 303
- Fire/smoke dampers at each rated crossing — not “where required.” Dampers
- Exhaust outlets dimensioned to intakes, openings, grade. 501.3
- Dryer duct: no screen, no screws, no fire damper. 504
- Condensate: if the primary drain stops, where does the water go? 307
- 30×30 service space drawn; roof hatch/walkway on the roof plan. 306
- Existing vs new vs demo identified. Change of occupancy
- FBC edition actually adopted — not 2024 IMC as if it were Florida law. FBC vs IMC
Print (browser print). Then what to send or intake.