/ Field knowledge · Kitchen + plumbing
The hood and the interceptor are one job.
A Type I hood on the mechanical sheets and no grease interceptor on the plumbing sheets is two comments, not a sequencing issue. The menu drives both.
What has to match
- Menu / equipment schedule decides Type I vs Type II and whether grease-laden waste exists.
- Hood and grease duct (IMC 506–508) on the M-sheets — type, slope, termination, makeup air, suppression.
- Grease interceptor on the P-sheets — basis, location, access, sample port. “Later” is a comment.
- Makeup air and dining OA are not the same pile of cfm. Run the 508 check.
- Sewer vs septic — if the street has no sewer, stop and open the OSTDS screen before anyone prices underground.
The usual failed VE
Keeping the Type I hood and cutting the interceptor to “fit the room.” That fails plumbing review, then fails the first grease inspection. See plumbing VE.
Tools: Type I / Type II · plumbing VE flags · hood vs interceptor check.
What to send
Architectural kitchen plan, equipment schedule, existing hood/termination photos on a remodel, plumbing plan or fixture list, and whether sewer is public.
If the hood and the interceptor are not on the same set
Send the menu/equipment schedule and both drawing sets — or the share link.