If the primary drain stops, where does the water go?

IMC 307 is water-damage prevention, not a pipe-size note. If the primary drain stops, the drawings have to say where the water goes and what shuts the unit down.

Educational 2024 IMC 307. Confirm the adopted FBC Mechanical edition. This is not a condensate design for your coil.

The proof chain on the M-sheets

The common redline

“Drain to nearest approved receptor” with no receptor, no slope, no overflow, and no tenant boundary. Equipment above a finished ceiling, tenant space, or electrical room is the highest-risk version of that note.

Source: Daily Code Talk — IMC 307 · tool: overflow-path check · access: IMC 306.

What to send

Unit location (above ceiling / closet / roof), architectural RCP if any, photos of the space below, and whether this is new or a replacement. A share link is enough.

If the drain note is the comment

Send the unit location and the ceiling below it. Masterbuild will say whether 307 is a drawing problem or a field problem.