/ Field knowledge · IMC 506.3.13

The grease outlet has to be dimensioned, not noted.

Mystery wall terminations, fans sitting on the roof without a 40-inch stack, and grease outlets next to OA intakes are the redlines Daily Code Talk #62 was written for.

Educational reading of 2024 IMC 506.3.13 (model code). Confirm the adopted FBC Mechanical edition and local amendments. This is not a termination design.

What 506.3.13 is asking the drawings to show

What plan review actually marks

Wall termination near windows. Outlet next to an OA intake. Roof fan too low. “Per code” with no dimensions. Show 40 IN MIN ABOVE ROOF, distance to intake, distance to property line / adjacent building, and discharge direction if you need the 5 ft exception.

Source: Daily Code Talk #62 · construction: 506.3 · slope: 506.3.7 · enclosure: 506.3.11 · fans: 506.5 · tool: termination check · kitchen: exhaust hub.

What to send

Roof plan or elevations, existing termination photos on a remodel, OA intake locations, and property-line / adjacent-building context. A share link is enough.

If the outlet is the comment

Send the roof plan and the photos. Masterbuild will say whether this is a 40-inch stack, a wall-termination path, or a coordination problem with intakes.