/ Field knowledge · IMC 506.3.7–506.3.9

If grease can pool, it will.

If grease can pool, it will. IMC 506.3.7–506.3.9 is drain-it-and-clean-it. Continuous slope toward the hood or a grease reservoir: minimum 1/4 in per 12 in (2%). Horizontal runs over 75 ft: 1 in per 12 in (8.3%). Cleanouts where sections cannot be cleaned from the hood or discharge — maximum 20 ft apart and within 10 ft of turns greater than 45 degrees. Most grease-duct failures are flat runs, missing cleanouts, or cleanouts nobody can reach.

Educational 2024 International Mechanical Code (IMC) 506.3.7–506.3.9 from Daily Code Talk. Confirm the adopted edition. Distinct from 506.3 materials / test-before-concealment and 506.3.11 enclosure. This is not a grease-duct design. Factory-built grease duct follows its listing.

On the set: slope arrows and slope rate on every horizontal grease-duct run. Cleanout locations dimensioned to turns and fans. Do not put a cleanout where the ceiling or a shaft makes it unreachable.

A 90-foot flat run with one cleanout at the hood

Grease pools. The inspector cannot clean past the first elbow. The wrap goes on anyway. That is a first-cycle comment and a fire-risk residue problem.

Source: Daily Code Talk — IMC 506.3.7–506.3.9 · tool: Slope / cleanout screen · construction: 506.3 · enclosure: 506.3.11.

What to send

The grease-duct plan with run lengths, turns greater than 45°, fan locations, and any cleanouts already shown.

If the grease duct is drawn flat

Send the plan. Masterbuild will say whether 506.3.7 still has no 2% slope — or 506.3.9 still has a 20 ft / 10 ft cleanout miss.

Send Project Background

+1 (786) 398-6940 · osmany.portal@masterbuildconsulting.com

Masterbuild provides engineering services under a written scope. Nothing on this page is project-specific engineering advice, a code interpretation for your project, or a representation about permit approval. Confirm the adopted edition. 2% / 8.3% slope, 20 ft / 10 ft cleanouts, 12×12 and 22×20 openings, and 1500°F gaskets are 2024 IMC 506.3 education from Daily Code Talk — not a grease-duct design. This page is not legal advice.