/ Field knowledge · IMC 502.7 / 502.7.7

A box fan at the roll-up is not 502.7.

Epoxy on a parking slab is still a flammable finish. IMC 502.7: provide exhaust wherever flammable finishes are sprayed or applied — including during construction. IMC 502.7.7: ventilate floor-resurfacing operations so vapors stay well below hazardous levels. A box fan in the garage door is not that path. “It’s temporary” is not a row. House Bill 803 does not exempt mechanical work.

Educational 2024 International Mechanical Code (IMC) 502.7 and 502.7.7 from Daily Code Talk. Confirm the adopted edition. Distinct from a spray booth with an interlock, a dip tank or powder booth, and 404 garage ventilation (the parking floor in normal use). This is not a coating specification and not a cfm. Daily Code Talk does not publish a resurfacing rate here — so this page does not either. Packet: 502.7 floor PDF · ES.

On the set: if the finish work is in the scope, show temporary or permanent exhaust, outdoor discharge, and 502.7 on the note. If the GC says “we will open the roll-up door,” that is the comment.

A box fan at the roll-up door, occupied offices on the same floor

Or a parking-garage recoat with only the 404 fans running. 404 is carbon monoxide in normal use. Floor-resurfacing is a 502.7 finish. Different contaminant. Different row.

Source: Daily Code Talk — IMC 502.2–502.7 · tool: Floor-resurfacing screen · spray: 502.7 spray · dip / powder: 502.7.7 tanks · 404: garage · permit: HB 803.

What to send

That floor-resurfacing or a flammable finish will be applied (including during construction), whether anyone is occupying adjacent space, and where the exhaust actually goes — outdoors, or a box fan at the door.

If the only exhaust is a box fan at the roll-up

Send the finish product and a photo of the space. Masterbuild will say whether 502.7 still has no exhaust during construction — or 502.7.7 still treats a garage recoat as 404.

Send Project Background

+1 (786) 398-6940 · osmany.portal@masterbuildconsulting.com

Masterbuild provides engineering services under a written scope. Nothing on this page is project-specific engineering advice, a code interpretation for your project, a coating specification, or a representation about permit approval. Confirm the adopted edition. Exhaust wherever flammable finishes are applied including during construction, and ventilation of floor-resurfacing so vapors stay well below hazardous levels, are 2024 IMC 502.7 / 502.7.7 education from Daily Code Talk — not a cfm and not a temporary-occupancy approval. HB 803 does not exempt mechanical work. This page is not legal advice.