/ Field knowledge · IMC 306.5

A portable ladder is not 306.5 access.

If reaching the unit means climbing higher than 16 feet above grade, IMC 306.5 wants a fixed interior or exterior access. No portable ladders. The route cannot require going over obstructions taller than 30 inches or walking on roofs steeper than 4:12. Group R-3 is exempt. Show the ladder, landings, and a receptacle on the permit set — not only in the specifications.

Educational 2024 International Mechanical Code (IMC) 306.5–306.5.2 from Daily Code Talk, with IBC guards/platforms and NFPA 70. Confirm the adopted edition. Distinct from service space (306.1–306.4). This is not a ladder design.

On the set: access path, ladder, 30×30 bottom landing, 30-in-deep top landing, catwalk widths, sloped-roof platforms, nearest service receptacle. Attachment points on or referenced from structural. Equipment tags reference the access detail number.

Portable ladder to a 20-foot RTU, no receptacle

Inspection hold and a fall-risk liability. Coordinate ladder type, landings, parapets, and power early — not at TCO.

Source: Daily Code Talk — IMC 306.5 · tool: Roof-access screen · 306.1: service space.

What to send

How high the unit sits above grade, roof slope if known, and whether a fixed ladder / stair and a service receptacle are shown.

If the only way up is a portable ladder

Send the roof height and the unit location. Masterbuild will say whether 306.5 still has no fixed access — or 306.5.2 still has no receptacle.

Send Project Background

+1 (786) 398-6940 · osmany.portal@masterbuildconsulting.com

Masterbuild provides engineering services under a written scope. Nothing on this page is project-specific engineering advice, a code interpretation for your project, or a representation about permit approval. Confirm the adopted edition. The 16-foot trigger, ladder dimensions, 4:12 slope, and NFPA 70 receptacle are 2024 IMC 306.5 education from Daily Code Talk — not a ladder or structural design. This page is not legal advice.