/ Field knowledge · conversions

A rule of thumb is not a load calculation.

A rule of thumb is not a load calculation. Cooling that “always” runs 1 cfm/ft² will be wrong on a Miami glass box and wrong on a warehouse. These identities are sea-level textbook factors used to check whether a number even belongs on the sheet — not to size a coil, a pump, or a chiller. 1 refrigeration ton = 12,000 Btu/h. Sensible air at sea level: Btuh ≈ 1.08 × CFM × ΔT (°F). Standard water: Btuh ≈ 500 × GPM × ΔT (°F). Air changes per hour: ACH = CFM × 60 ÷ room volume (ft³). Energy efficiency ratio (EER) and coefficient of performance (COP): COP ≈ EER ÷ 3.412.

Educational field identities. Confirm density, glycol, altitude, and wet-bulb before anyone treats the result as a design. This page is original Masterbuild education. It is not a reproduction of any vendor “green sheet,” pipe-sizing table, or psychrometric chart, and it does not replace ASHRAE load methods or the PE of record.

On the set: show the identity you used (1.08, 500, 12,000) and the ΔT. If glycol or altitude applies, say so. If the coil leaving-air is wet, total cooling is CFM × 4.5 × Δh (enthalpy) at sea level — that Δh comes from a psychrometric state, not from a ΔT guess.

Sized from “1 cfm/ft²” and “2.4 gpm/ton” with no load

Those thumbs assume a ΔT and a climate that may not be this project. Miami latent, glass, and 24-hour occupancy blow them up. Use the estimator as a sanity check, then send the room areas, occupancy, and envelope so the PE can run a real load.

Related: Conversion screen · outdoor air: 401.4 · hydronic flood/weather: duct exposure · refrigerant class: ASHRAE 34 / EPA 608.

What to send

The number you are trying to check (cfm, gpm, tons, EER), the ΔT or room volume behind it, and whether glycol or a non-sea-level site is in play. Do not send a screenshot of a vendor green sheet as the design basis.

If the schedule was filled from a thumb

Send the areas and the occupancy. Masterbuild will say whether 1.08 / 500 still has no ΔT on the sheet — or the tonnage still has no load behind it.

Send Project Background

+1 (786) 398-6940 · osmany.portal@masterbuildconsulting.com

Masterbuild provides engineering services under a written scope. Nothing on this page is project-specific engineering advice, a code interpretation for your project, or a representation about permit approval. 1.08, 500, 12,000 Btu/h per ton, ACH = CFM × 60 ÷ volume, and COP ≈ EER ÷ 3.412 are sea-level textbook identities for education only. They do not size equipment, do not set a glycol correction, and do not replace an ASHRAE load. This page does not reproduce third-party green sheets or psychrometric charts. This page is not legal advice.