/ Field knowledge · IMC 507.1 exceptions

“No hood required” is not a designer preference.

Commercial hoods are Type I or Type II. If any appliance under one hood requires Type I, the entire hood is Type I. “No hood required” is not a designer preference. IMC 507.1 exceptions only hold when the listing is on the drawings: UL 710B recirculating, listed integral downdraft (NFPA 96), smoker ovens with integral exhaust, UL 2162 wood-fuel ovens, UL 197 reduced-grease electric cooking, UL 921 dishwashers with self-contained condensing, or the heat/moisture-only path with space exhaust at 0.70 cfm/sf and 100 sf minimum per appliance.

Educational 2024 International Mechanical Code (IMC) 507.1 general exceptions from Daily Code Talk. Confirm the adopted edition. Distinct from 507.2 Type I construction and 505 vs 507. This is not a listing determination. Type I is always the “safe upgrade,” but it then triggers Type I installation rules.

On the set: M-001 “IMC 507 EXCEPTIONS” note with the exception number, listing standard, and model. Hood/appliance schedule: listing standard + model for every exception-driven decision. Heat/moisture path: 0.70 cfm/sf and 100 sf per appliance on the ventilation schedule. Coordinate with the authority having jurisdiction (AHJ) before issuing when relying on a 507.1 exception. Undocumented exceptions are the most common 507.1 comment.

“Recirc hood” with no UL 710B

Or a downdraft with no NFPA 96 listing. Or skipping hood exhaust and also skipping 0.70 cfm/sf. That is still a Type I or Type II hood — plus a first-cycle comment.

Source: Daily Code Talk — IMC 507.1 exceptions · tool: Exception screen · Type I: 507.2 · 505: domestic vs commercial.

What to send

The appliance lineup, any “no hood” or recirculating claim, and the listing (UL 710B / 197 / 921 / 2162 / NFPA 96) if one exists.

If the set says “no hood required” with no listing

Send the lineup. Masterbuild will say whether 507.1 still has an undocumented exception — or one steam table is still dragging the whole hood to Type I.

Send Project Background

+1 (786) 398-6940 · osmany.portal@masterbuildconsulting.com

Masterbuild provides engineering services under a written scope. Nothing on this page is project-specific engineering advice, a code interpretation for your project, or a representation about permit approval. Confirm the adopted edition. UL 710B / 197 / 921 / 2162, NFPA 96 downdraft, 0.70 cfm/sf, and 100 sf per appliance are 2024 IMC 507.1 education from Daily Code Talk — not a listing determination. This page is not legal advice.