Flex does not cross the rated line.

IMC 607.7: flex does not cross a rated assembly. No gage substitution. No “short run” allowance. If the boundary is rated, the flex stops and listed sheet steel with the right 607.5 / 607.6 protection carries through.

Educational 2024 IMC 607.7. Confirm adopted edition and the life-safety plan. This is not a damper selection. Air connectors — the listed flexible connectors at equipment — carry the same restriction. They are a terminal device, not a rated-penetration component.

Last three feet through the corridor wall

Follow every flex run back to hard duct. If it crosses a rated wall, shaft, ceiling membrane, or floor, correct it before the boundary is concealed. Overlay the life-safety plan on the M-sheet before anyone cuts flex.

Source: DCT 607.7 · tool: flex screen · dispersion: 603.17 · outlets: 603.18 · dampers: 607 · construction: 603.

What to send

The RCP, the rated-wall plan, and whether any flex is shown through a corridor, shaft, or rated ceiling.

If the flex tails through the corridor

Send the RCP. Masterbuild will say whether 607.7 even allows that run — or the flex has to stop and hard duct take the rated line.