/ Field knowledge · IMC 607.7

Flex does not cross the rated line.

Classify the listed product before drawing a crossing. Under 2024 IMC 603.6.2.2, a flexible air connector cannot pass through any wall, floor or ceiling, even an unrated one. Section 607.7 separately prohibits flexible ducts and connectors through fire-resistance-rated assemblies. A smoke designation needs its own assembly-rating and damper review.

Educational 2024 IMC 603.6.2.2 and 607.7. Confirm the adopted edition, the product listing, and the architectural life-safety plan. This is not a damper selection. Read the connector rule and rated-assembly rule. Packet: English PDF · PDF en español.

A connector through an unrated corridor wall

That is prohibited by 603.6.2.2 even if the wall has no fire-resistance rating. Overlay the life-safety plan on the mechanical set, distinguish duct from connector, and move the transition before the boundary.

Source: 2024 IMC Chapter 6 · DCT 607.7 · tool: flex screen · dispersion: 603.17 · outlets: 603.18 · dampers: 607 · construction: 603.

What to send

The reflected ceiling plan, UL 181 product classification, architectural wall/floor/ceiling and smoke designations, and proposed flex-to-rigid transition and penetration details.

If a flex run reaches a boundary

Send the product label and boundary detail. MasterBuild can scope the connector prohibition, rated-assembly condition and separate damper review.