Over 2,000 cfm, the return needs a detector.

IMC 606: return systems over 2,000 cfm need listed duct smoke detection. Combined supply/return capacity counts. A detector in the wrong place, or a shutdown that never got wired, fails commissioning.

Educational 2024 IMC 606. Confirm adopted edition and NFPA 72. This is not a fire-alarm design.

Wrong velocity / no interlock

DCT: detectors in ducts with velocities outside the listed range (typically 300–4000 fpm) will not detect reliably. The most common commissioning failure is detector activation with the AHU still running.

Source: DCT 606 · install: 606.3 · tool: 2,000 cfm check · 512: smoke control.

What to send

AHU/RTU schedule cfm, whether returns are combined, and number of stories on the riser.

If the RTU is over 2,000 cfm and there is no detector

Send the schedule cfm. Masterbuild will say whether 606.2.1 is even on the path — or the combined returns already crossed 2,000.