/ Field knowledge · IMC 604.13

Do not line the wet coil discharge.

IMC 604.13: exposed internal insulation that is not impermeable to water cannot run from the cooling-coil exit to the downstream end of the drain pan. Generic lined duct through that section is the comment — and the mold later.

Educational 2024 IMC 604.13. Confirm adopted edition. This is not an insulation specification. Internal insulation exposed to the airstream needs a UL 181 durability basis.

Liner through the drain pan

If a superintendent can stand at the coil discharge and still ask where the pan ends, or whether the exposed liner is water-impermeable, the drawings are not clear enough. Wet liner is an IAQ problem that comes back after remediation if the root cause stays.

Source: DCT 604.13 · insulation: 604 · condensate: 307.

What to send

The AHU / coil section and whether the downstream duct is shown lined.

If the liner runs through the coil discharge

Send the AHU section. Masterbuild will say whether 604.13 even allows that product — or the drain-pan limit was never drawn.