“Ventilated per code” is not a calculation.

IMC 406.1: crawl spaces and attics are ventilated naturally per IBC openings, or mechanically with both supply and exhaust. A note that says “ventilated per code” with no math is the comment.

Educational 2024 IMC 406.1. Confirm the adopted FBC Mechanical edition and IBC opening rules. This is not a vent-area design.

Only exhaust, no supply

Exhaust without a makeup path is the redline. Fan cfm sized to a catalog number instead of 0.02 cfm/ft² at external static (duct, screens, hoods) is the next one.

Source: DCT 406 · transfer: 501.4 · tool: attic / crawl check.

What to send

Attic or crawl floor area, whether openings exist, and whether a fan is proposed. Photos of existing vents help on a replacement.

If the set says “ventilated per code”

Send the attic or crawl area and whether this is natural openings or a fan. Masterbuild will say whether 406.1 math is even on the drawings.