/ Field knowledge · IMC 507.3

Type II is not “general exhaust.”

IMC 507.3: Type II is steam, heat, and combustion without grease. Calling it “general exhaust” is a first-cycle comment. Lock the appliance list before the permit — a griddle under a Type II hood is the expensive change.

Educational 2024 IMC 507.3. Confirm adopted edition. Distinct from the Type I path on commercial kitchen ventilation. If any appliance produces grease-laden vapors, Type I controls regardless of the hood label.

Hood schedule columns from Daily Code Talk: appliance type (light-duty / DW) | NET cfm/lf | material/ga. If any appliance is changed to a grease-producing type after permit, upgrade to Type I before occupancy.

Steam kettle to griddle

The most common Type II inspection failure is an after-permit menu change. Confirm with the operator that appliance types are final before the set is filed. Missing NET cfm is a consistent plan-review flag.

Source: DCT 507.3 · ducts: 506.4 · Type I: 507.2 · makeup: makeup air.

What to send

The appliance list and whether anything produces grease-laden vapor.

If the menu is not locked

Send the appliance list. Masterbuild will say whether 507.3 even has a Type II path — or this is already a Type I grease-duct conversation.

Send Project Background

+1 (786) 398-6940 · osmany.portal@masterbuildconsulting.com

Masterbuild provides engineering services under a written scope. Nothing on this page is project-specific engineering advice, a code interpretation for your project, or a representation about permit approval. Confirm the adopted edition. NET cfm and gages below are 2024 IMC model-code education from Daily Code Talk — not a hood selection.