Windows are not ventilation until the 4% is on the sheet.

IMC 402: natural ventilation is openable area, not “there are windows.” Four percent of the floor area. Occupants have to be able to operate it.

Educational 2024 IMC 402. Confirm adopted edition and energy-code override. This is not a ventilation design. Managed buildings that keep windows locked are not a 402 strategy. Packet: 402 PDF · ES.

Windows on one wall, no table

Total 4% on the same wall is not a documented airflow path. Use free area of the grille/transom, not the nominal frame size. Keep operable openings away from exhaust outlets the same way you would an OA intake.

Source: DCT 402 · tool: 4% screen · mechanical: 403.

What to send

Floor area by room, which openings actually operate, and whether the owner’s policy is to keep windows closed.

If the comment is “show the 4%”

Send the room areas and the window schedule. MasterBuild will say whether 402 even works — or this building needs 403 mechanical OA.

Send Project Background

+1 (786) 398-6940 · osmany.portal@masterbuildconsulting.com

MasterBuild provides engineering services under a written scope. Nothing on this page is project-specific engineering advice, a code interpretation for your project, or a representation about permit approval.