/ Field knowledge · IMC 403.3.2

Townhouses do not use the office OA table.

IMC 403.3.2: Group R-2 / R-3 / R-4, three stories or fewer. Whole-house OA is Equation 4-9, not Table 403.3.1.1. The 30% reduction needs OA ducted to each bedroom and at least one of the living room, dining room, or kitchen — and a balanced system.

Educational 2024 IMC 403.3.2. Confirm adopted edition. Distinct from 403.3.1 Vbz/Ez. This is not a fan selection. Packet: 403.3.2 PDF · ES.

For the reduction, document that the whole-house outdoor-air system is balanced, with the supply and exhaust airflows and commissioning evidence. The model reduction conditions do not state a generic numeric "tight tolerance"; use the applicable design and verification basis. Design for delivered cfm and verify at the terminals. Label the control "Whole-House Ventilation" so it is not disabled.

30% off with no bedroom OA

Missing corridor 0.06 cfm/ft² is the other common redline. If cycling, the controls must enable at least one hour of operation in each four-hour period and the four-hour average must meet the applicable Equation 4-9 basis. More airflow cannot make a shorter cycle qualify. Document the schedule and delivered cfm; confirm the adopted text before combining separate exceptions.

Source: ICC 2024 IMC §403.3.2 · DCT 403.3.2 · tool: Eq. 4-9 screen · path: 401.2 · dryer: 504.

What to send

Afloor, bedroom count, the OA delivery points (each bedroom plus at least one living/dining/kitchen space), and the supply/exhaust balance evidence.

If the townhouse set used Table 403.3.1.1

Send Afloor and Nbr. MasterBuild will say whether 403.3.2 even has Equation 4-9 — or the 30% cut was assumed.

Send Project Background

+1 (786) 398-6940 · osmany.portal@masterbuildconsulting.com

MasterBuild provides engineering services under a written scope. Nothing on this page is project-specific engineering advice, a code interpretation for your project, or a representation about permit approval. Confirm the adopted edition. Equation 4-9 and Ez-free rates below are 2024 IMC education from Daily Code Talk — not a sealed outdoor-air design.