Daily Code Talk #168IMC 902 Masonry Fireplaces

A masonry fireplace may appear on the mechanical plans, but Chapter 9 does not contain the full construction criteria.

Permit Proof Chain

01Code TriggerIdentify why the section applies.
02Sheet EvidenceShow the requirement where the reviewer needs it.
03Coordination OwnerTie the requirement to the responsible discipline or party.
04Field ProofConfirm the installed condition can be verified.

A masonry fireplace may appear on the mechanical plans, but Chapter 9 does not contain the full construction criteria. IMC 902 sends part of the review directly to the Building Code.

902.1 General

Masonry fireplaces must be constructed in accordance with the International Building Code. The IMC identifies the equipment; the actual masonry construction requirements are handled through the IBC. Masterbuild seals MEP. We do not seal masonry fireplace construction.

902.2 Fireplace accessories

Listed and labeled fireplace accessories must be installed in accordance with the conditions of their listing, follow the manufacturer’s installation instructions, and comply with UL 907. An accessory is not automatically acceptable because it physically fits.

Field tip

For specialty equipment, “listed” is not just a product characteristic. The installation itself has to remain within the conditions of that listing. Hub: 902 hub. Next: IMC 903.

Code basis

2024 IMC model-code education from the owner-provided Daily Code Talk. Confirm adopted IBC/IMC editions. Not a fireplace design.