Daily Code Talk #129IMC 801.8 - Abandoned Inlet Openings(7/21)

Removing an appliance doesn't close its chimney opening for you. IMC 801.8 requires every abandoned inlet to be sealed by an approved method - a step existing-building projects routinely skip.

Permit Proof Chain

01Code TriggerIdentify why the section applies.
02Sheet EvidenceShow the requirement where the reviewer needs it.
03Coordination OwnerTie the requirement to the responsible discipline or party.
04Field ProofConfirm the installed condition can be verified.

IMC 801.8 covers a step that's easy to overlook on replacement and renovation work: when an appliance is removed, relocated, or converted, its old chimney or vent opening doesn't take care of itself. It has to be closed by an approved method.

Plain-English Highlights

Abandoned inlet openings in chimneys and vents must be closed by an approved method. This comes up constantly on existing-building work: appliance replacement, boiler or furnace removal, water heater relocation, conversion from chimney venting to direct vent, conversion from fuel-fired to electric equipment, and demolition of old vent connectors all leave openings that need to be addressed - not just left as-is because the appliance is gone.

Permit Proof Chain

Identify every appliance being removed, replaced, or relocated -> trace its existing connector and chimney/vent inlet opening -> confirm whether the chimney/vent remains in service for another appliance -> specify an approved closure method and material -> verify the closure is compatible with the chimney/vent system.

Where To Show It

M-001: demolition and vent abandonment notes. M-101: existing appliance, chimney, and vent locations. M-501: abandoned opening closure detail. M-601: appliance replacement schedule and venting basis. A/LS sheets: rated walls, shafts, chimney enclosures. P sheets: water heater, boiler, fuel, and oil coordination.

**Do** - Identify every abandoned chimney or vent opening on the drawings, not just the new appliance's vent. - Show connector removal and the closure method together. - Confirm closure materials are compatible with the chimney or vent system in use. - Coordinate with existing chimney reuse and liner requirements where the chimney stays in service.

**Do Not** - Leave old vent openings unaddressed on the drawings. - Use "cap by contractor" as a substitute for a reviewable detail. - Assume abandoned openings are harmless to draft or fire separation. - Reuse a chimney without checking for old, unaddressed tie-ins.

Masterbuild QA Lens

On any replacement or renovation scope, ask where the old appliance used to connect - not just where the new one connects. An abandoned opening left unsealed undermines draft on the remaining system and can be a fire-separation gap.

Drawing / Submittal Check

For every appliance removal or replacement on the demolition plan, confirm there's a matching closure detail or note - an appliance schedule that shows removals with no corresponding abandonment note is incomplete.

Common Review Risk

The most common gap is a multi-appliance chimney where one unit is replaced and reconnected, but an old tie-in point from a previous appliance is never traced or closed.

When To Escalate

Escalate any multi-story or common-vent chimney where one appliance is being abandoned while others remain in service, since the closure method can affect draft for the remaining appliances.

Field Tip

On replacement projects, trace every old vent connector before signing off. The drawings should show both the new vent path and the approved closure of whatever opening the old appliance left behind.