Daily Code Talk #133IMC 801.12 Chimney Entrance / 801.13 Cleanouts(11/21)

IMC 801.12 and 801.13 govern chimney access, maintenance, and proper connector location - small dimensions with real field consequences.

Permit Proof Chain

01Code TriggerIdentify why the section applies.
02Sheet EvidenceShow the requirement where the reviewer needs it.
03Coordination OwnerTie the requirement to the responsible discipline or party.
04Field ProofConfirm the installed condition can be verified.

IMC 801.12 and 801.13 are small-dimension requirements with real field consequences: where the connector enters the chimney, and whether the chimney can actually be inspected and cleaned after construction. Both are about serviceability - and both are easy to lose behind a generic "connect to existing chimney" note.

Plain-English Highlights

IMC 801.12 (Chimney Entrance): connectors must enter the chimney flue at a point not less than 12 inches above the lowest portion of the interior of the chimney flue. That 12-inch separation keeps the connector from discharging directly into the bottom of the flue where debris, condensate, ash, or soot may collect. For plan review, the connector elevation matters - the drawings should show the appliance connector entering the chimney at a compliant height.

IMC 801.13 (Cleanouts): masonry chimney flues must have a cleanout opening with a minimum height of 6 inches, with the upper edge of the opening at least 6 inches below the lowest chimney inlet opening, and a tight-fitting, noncombustible cover. Exception: a cleanout is not required for chimney flues serving masonry fireplaces when access is provided through the fireplace opening.

Permit Proof Chain

Appliance connector routing -> chimney entrance elevation shown (not less than 12 inches above the lowest interior flue portion) -> cleanout located below the lowest inlet (6-inch minimum height, upper edge at least 6 inches below the lowest inlet opening) -> tight-fitting noncombustible cover -> access preserved after finishes and casework -> inspection and maintenance path verified.

Where To Show It

M-001: chimney connector and cleanout notes. M-101: appliance location and chimney connection point. M-501: connector entrance, cleanout, cover, liner, and access details. M-601: appliance schedule with chimney / venting basis. A/LS sheets: chimney, fireplace, shaft, wall, and rated assembly coordination.

**Do** - Show the chimney connector entrance elevation. - Provide the required 12-inch separation above the lowest interior flue portion. - Show masonry chimney cleanout size, location, and cover. - Confirm cleanout access is maintained after construction.

**Do Not** - Use "connect to existing chimney" without showing the connection point. - Hide cleanouts behind finishes, equipment, or casework. - Omit the noncombustible tight-fitting cleanout cover. - Assume fireplace access satisfies cleanout requirements unless the exception actually applies.

Masterbuild QA Lens

The vertical relationship IS the review: connector inlet above, cleanout below, both accessible. A chimney detail that doesn't show elevations can't be reviewed against 801.12 or 801.13 - it can only be assumed, and assumptions are what reinspections are made of.

Drawing / Submittal Check

For each appliance connected to a chimney, find two things on the details: the connector entrance elevation, and the cleanout with its size, location, and cover. If either is missing - or the connection is covered by a bare "connect to existing" note - the submittal is incomplete, not field-resolvable.

Common Review Risk

Existing-building reuse is where these sections bite: an old chimney reused for a new appliance with no entrance elevation shown, a cleanout that is missing, blocked, undersized, or - most common - concealed behind new finishes, equipment, or casework once construction ends. That leads to soot buildup, blocked flues, poor draft, corrosion, combustion-product spillage, and failed inspections.

When To Escalate

Escalate existing chimney reuse without a documented condition and liner basis, any configuration where the cleanout cannot be located below the lowest inlet opening, and fireplace-exception claims where real access through the fireplace opening is doubtful.

Field Tip

When reviewing a masonry chimney detail, check the vertical relationship: connector inlet above, cleanout below, and both accessible. If that relationship is not shown, the chimney detail is incomplete.