Daily Code Talk - IMC 309: Temperature Control

IMC 309 is the baseline heating-capability check: occupiable interior spaces need an active or passive heating system capable of maintaining 68 F on the design heating day unless an exception applies.

Permit Proof Chain

01Installation BasisIdentify listing, manufacturer limits, and code trigger.
02Access / ClearanceShow service space and realistic field access.
03Coordination OwnerTie structure, electrical, plumbing, and architectural constraints together.
04Field VerificationConfirm the installed condition can be inspected and maintained.

IMC 309 is short, but it controls an important design assumption: spaces intended for human occupancy need heat. Portable space heaters do not count as the compliance strategy.

Plain-English Summary

Interior spaces intended for human occupancy must be capable of maintaining at least 68 F at a point 3 feet above the floor on the design heating day. The code allows active or passive heating systems, but the requirement has to be met by the building design, not temporary plug-in heaters.

Exception Check

The key exceptions are spaces where the primary purpose is not associated with human comfort and Group F, H, S, and U occupancies. Do not apply the exception just because a space is normally unoccupied; confirm the occupancy and intended use.

Permit Proof Chain

Space use -> occupancy classification -> whether human occupancy and comfort apply -> design heating day basis -> active or passive heating system -> capacity/load documentation -> thermostat/control location -> exception basis if heat is omitted.

Masterbuild QA Lens

The risk is a shell, storage, back-of-house, or support space being shown without heat because nobody expected comfort complaints, while the occupancy or use still triggers the 68 F requirement.

Drawing / Submittal Check

On schedules and floor plans, identify which spaces are heated, which are exempt, and how the heating system satisfies the design day. If heat is omitted, state the exception basis cleanly.

Field Tip

During existing-building reviews, look for converted storage rooms, offices carved out of warehouses, and tenant back rooms. The new use can trigger heating even when the old space did not need it.