Sparky Edition #024NEC 110.17–110.25 Servicing, Reconditioned Equipment, Markings & Disconnects (7/10)

Article 110 shifts from installation to what happens after equipment is in service: servicing, reconditioning, markings, fault-current updates and disconnect identification.

By Osmany Portal, PE

Permit Proof Chain

01Code TriggerIdentify why the section applies.
02Sheet EvidenceShow the requirement where the reviewer needs it.
03Coordination OwnerTie the requirement to the responsible discipline or party.
04Field ProofConfirm the installed condition can be verified.

110.17 Servicing of equipment

Servicing is performed by qualified persons, following the manufacturer’s instructions and applicable standards, or as otherwise approved by the AHJ. Replacement parts come from the manufacturer, are designed by an engineer experienced with that equipment, or are approved by the AHJ.

110.18 Arcing parts

Parts that normally produce arcs, sparks, flames or molten metal are enclosed or separated and isolated from combustible material.

110.20–110.21 Reconditioned equipment and marking

Reconditioned equipment is permitted unless the NEC prohibits it for that equipment. Where listing is required, it is listed or field labeled as reconditioned. Equipment carries durable identification and its ratings; reconditioned equipment also shows who reconditioned it, the date, and that it was reconditioned.

110.22–110.23 Disconnects and current transformers

Each disconnecting means is legibly marked to show its purpose unless that is evident. Where more than one source exists, the marking also identifies the source unless the arrangement makes it evident. Unused current transformers associated with potentially energized circuits are short-circuited.

110.24 Available fault current

Service equipment at other than dwelling units is field marked with the available fault current and the date of the calculation. When a modification changes the available fault current, it is verified or recalculated and the marking updated.

110.25 Lockable disconnecting means

Where a disconnect must be lockable open, the locking provision stays in place with or without the lock installed.

Why it matters

Renovation work reuses existing equipment constantly. Ask who serviced it, whether the replacement parts are acceptable, whether the markings are still accurate, whether a new transformer, utility change or generator moved the fault current, and whether the disconnect can actually be locked open.

Where to show it

As applicable: the single-line diagram and panel schedules (source identification), equipment schedules noting reconditioned items, the fault-current table or study with its date, and specifications for labels and lockable disconnects.

Field tip

When equipment has been modified, do not assume the old label still tells the truth. Verify the condition, source identification, servicing history and available fault current before relying on existing markings. In Miami-Dade this is exactly the evidence an electrical building recertification asks for. Next: #025 — NEC 110.26 Working Space.

Code basis

NEC 2026 Article 110.17–110.25 education from the owner-provided Daily Code Talk. Confirm the locally adopted NEC edition and amendments. Not a fault-current study or a reconditioning approval.

PE-led project support

Need this applied to a live project?

MasterBuild Consulting helps owners, architects, GCs, and project teams turn code questions into permit-ready MEP decisions before review comments, field changes, or inspection issues cost more time.

Sparky Edition uses the 2026 NEC as model-code education. Verify the locally adopted NEC edition, amendments, listings, and AHJ path before project use.

Related Daily Code Talk posts