🧠 Plain English: 404.1 — Garage ventilation must run continuously OR automatically via CO + NO₂ detectors listed to UL 2075 installed per MI. Automatic systems: Full-On ≥0.75 cfm/ft²; Standby ≥0.05 cfm/ft² of floor area served. 404.2 — Accessory offices/booths/waiting rooms connecting to a public garage must be positive pressure to the garage and ventilated per 403.3.1.
🧮 Step-by-Step: Full-On cfm = 0.75 × ft². Standby cfm = 0.05 × ft². Controls: CO/NO₂ thresholds for Standby ↔ Full-On; fail-safe to Full-On on detector/BAS fault. Accessory rooms: supply > exhaust to maintain positive pressure.